HomeMy WebLinkAboutOrdinance 2914 N.C.S. 12/01/2025 Ordinance No. 2914 N.C.S. Page 1
EFFECTIVE DATE
OF ORDINANCE
January 1, 2026
ORDINANCE NO. 2914 N.C.S.
Introduced by: Janice Cader Thompson Seconded by: Brian Barnacle
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF PETALUMA ADOPTING BY
REFERENCE THE 2025 EDITION OF THE CALIFORNIA BUILDING STANDARDS CODE,
INCLUDING: PART 1, 2025 CALIFORNIA ADMINISTRATIVE CODE; PART 2, 2025 CALIFORNIA
BUILDING CODE; PART 2.5, 2025 CALIFORNIA RESIDENTIAL CODE; PART 3, 2025
CALIFORNIA ELECTRICAL CODE; PART 4, 2025 CALIFORNIA MECHANICAL CODE; PART 5,
2025 CALIFORNIA PLUMBING CODE; PART 6, 2025 CALIFORNIA ENERGY CODE; PART 7,
2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE; PART 8, 2025 CALIFORNIA
HISTORICAL BUILDING CODE; PART 10, 2025 CALIFORNIA EXISTING BUILDING CODE;
PART 11, 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE; PART 12, 2025
CALIFORNIA REFERNCED STANDARDS CODE, LOCAL AMENDMENTS TO SPECIFIED
PROVISIONS OF THE CALIFORNIA BUILDING STANDARDS CODE, AND 2024
INTERNATIONAL PROPERTY MAINTENANCE CODE
WHEREAS, every three years, the City of Petaluma adopts local amendments to the State Building
Standards Code, Residential, and Fire Codes, and
WHEREAS, the State-adopted 2025 California Building Standards Code become effective on January 1,
2026; and
WHEREAS, the City seeks to amend its Municipal Code to adopt the 2025 California Building Standards
Code, and the 2024 International Property Maintenance Code by reference; and
WHEREAS, California Health and Safety Code Sections 17958.7; 17958.5, and 17958.7 require the local
governing body of a city before making any modifications or changes to the California Building Standards Code,
to make express findings that such modifications or changes are reasonably necessary because of local climactic,
geological, or topographical conditions; and
WHEREAS the City of Petaluma finds that a departure from the California Building Standards Code is
reasonably necessary due to local climactic, geological, or topographical conditions.
NOW, THEREFORE, be it ordained by the Council of the City of Petaluma as follows:
SECTION 1. AMENDMENT OF PREVIOUS BUILDING CODES. Sections 17.04.010, and 17.04.020 of the
Petaluma Municipal Code, entitled “California Codes based on International Codes for Construction and
Regulation of Buildings and Structures” are hereby amended as shown in Section 4.
SECTION 2. FINDINGS. The City Council of the City of Petaluma finds that in order to best protect the health,
safety and welfare of the citizens of the City of Petaluma, the standards of building within the City must conform
with state law except where local climatic, geological, and topographic conditions warrant more restrictive
regulations. Therefore, the City Council hereby adopts the current state building codes, contained in California
Building Standards Code Title 24, and other uniform codes governing the construction and regulation of
buildings and structures subject to the modifications and amendments contained herein.
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 2
Pursuant to California Health and Safety Code Section 17958.7, the City Council makes the factual findings set
forth in “Exhibit A” attached hereto and incorporated herein by reference, and finds that the amendments
contained in this ordinance to the California Building Standards Code Title 24, Parts 1, 2, 2.5, 3, 4, 5, 6, 8, 10,
12 and the 2024 International Property Maintenance Code are reasonably necessary because of the local climatic,
geological or topographical conditions described in Exhibit A.
SECTION 3. CURRENT BUILDING CODES ADOPTED.
Chapter 17.04 of the Petaluma Municipal Code, entitled “California Codes based on International Codes for
Construction and Regulation of Buildings and Structures” is hereby added to read as follows:
17.04.010: Adoption of California Codes based on International Codes
Pursuant to Section 50022.2 of the California Government Code, the following codes are adopted by reference,
including the amendments listed in this chapter which are made pursuant to the findings of fact set forth in th is
ordinance.
A. Part 1—2025 California Administrative Code;
B. Part 2—2025 California Building Code based on the 2024 International Building Code, including
Appendix J (Grading), Appendix N (Replicable Buildings), and Appendix Q (Emergency Housing) in
their entirety except as amended in Section 17.04.020;
C. Part 2.5— 2025 California Residential Code based on the 2024 International Residential Code
including Appendix BG (Sound Transmission), Appendix BH (Automatic Vehicular Gates),
Appendix BB (Tiny Houses), Appendix BI (Light Straw-Clay construction), Appendix CI (Swimming
Pool Safety Act), and Appendix CH (Emergency Housing) in their entirety except as amended in
17.04.020;
D. Part 3—2025 California Electrical Code based on the 2023 National Electrical Code;
E. Part 4—2025 California Mechanical Code based on the 2024 Uniform Mechanical Code
F. Part 5—2025 California Plumbing Code based on the 2024 Uniform Plumbing Code;
G. Part 6—2025 California Energy Code;
H. Part 7 2025 California Wildland-Urban Interface Code;
I. Part 8—2025 California Historical Building Code;
J. Part 10—2025 California Existing Building Code based on the 2024 International Existing Building
Code;
K. Part 11—2025 California Green Building Standards Code including Appendix A4 at Tier 1 level
requirements (Residential Voluntary Measures) and Appendix A5 at Tier 1 level requirements
(Nonresidential Voluntary Measures);
L. Part 12—2025 California Referenced Standards Code;
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 3
M. 2024 International Property Maintenance Code;
All references to permit fees in the codes adopted by reference are deleted pursuant to this ordinance. Instead,
the permit fees applicable in Petaluma will be fixed by the fee schedules adopted by the city council by resolution.
17.04.020 Amendments Made in California Building Codes Parts 2, 2.5, 8, 10, and 11.
Part 2 of the 2025 California Building Standards Code, California Building Code, as adopted in section
17.04.010, is hereby amended to include the following additions, amendments and deletions:
California Building Code
Chapter 1 – Administration
Section 105.2 Item Building: 1. is hereby amended to read as follows:
105.2 Item Building: 1.: One-story detached accessory structures used as tool and storage sheds, playhouses and
similar uses, provided the floor area is not greater than one hundred twenty square feet (120 sq.) (11 m2), there
are no wall finishes such as, but not limited to, gypsum wallboard, plaster, stucco, or paneling placed on any
interior surface of any wall and/or partition, and no electrical, mechanical or plumbing systems are contained
within the structure. These structures are still regulated by Section 710A, despite exemption from permit.
Section 115.1 and 115.2 are hereby amended to read as follows, and a new section 115.5 is created:
115.1 Authority. Where the building official finds any work regulated by this code being performed in a manner
contrary to the provisions of this code or in a dangerous or unsafe manner, without a permit, beyond the scope
of the issued permit, in violation of the Petalum a Municipal Code or Zoning Ordinance, the building official is
authorized to issue a stop work order.
115.2 Issuance. The stop work order shall be in writing, be posted in a visible location near the location where
the work is being conducted, and shall be given to the owner of the property, the owner’s authorized agent or the
person performing the work. Upon issuance of a stop work order, the cited work shall immediately cease. The
stop work order shall state the reason for the order and the conditions under which the cited work is authorized
to resume.
115.5—Fee. An additional investigation fee of at least the permit fee and up to five times the permit fee shall be
added to each permit subject to a stop work order according to the building official’s determination. Licensed
contractors and repeat offenders are to be assessed investigation fee at five times the permit fee.
Chapter 2 – Definitions
Section 202 is amended to amend and add the following definitions:
JUNIOR ACCESSORY DWELLING UNIT. [HCD] A unit that is no more than 500 square feet in size and
contained entirely within an existing single-family structure. A junior accessory dwelling unit may include
separate sanitation facilities, or may share sanitation facilities with the existing structure. (See Government Code
Section 65852.22.)
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 4
KITCHEN. That portion in a residential dwelling unit that is a room or area used for cooking, food storage and
preparation and washing dishes, including associated counter tops and cabinets, refrigerator, stove, ovens and
floor area.
Substantial Remodel. Any repair, reconstruction, rehabilitation, alteration, addition or other improvement of a
building or structure that is any of the following:
(1) An existing building or structure not classified as Group R-3 occupancy that undergoes any addition of
floor area that is equal to or exceeds 10 percent of the existing gross floor area of the building or structure.
(2) An existing building or structure classified as a Group R-3 occupancy that undergoes any addition of
floor area that is equal to or exceeds 50 percent of the existing gross floor area of the building or structure.
(3) An existing building or structure that undergoes any combination of repair, reconstruction, rehabilitation,
alteration, addition or other improvement to floor area of the building or structure that is equal to or
exceeds 50 percent of the existing gross floor area of the building or structure.
(4) If in the determination of the Building Official a building or structure has sustained substantial damage,
as defined by Section 202 of the California Building Code as amended hereby, any combination of repair,
reconstruction, rehabilitation, alteration, addition or other improvement are considered substantial
improvement regardless of the actual work performed.
The Code Official shall aggregate any combination of repair, reconstruction, rehabilitation, alteration, addition,
or other improvements to a building or structure within a three (3) year period, and if the combined affected
gross floor area of the building or structure is equal to or exceeds 50% of gross floor area of the building or
structure, the aggregated work shall constitute substantial improvement and the building shall be subject to the
fire sprinkler requirement.
Nuisance Alarm. An unwarranted alarm caused by mechanical failure, malfunction, improper installation or
lack of proper maintenance, system servicing testing, construction activities, ordinary household activities, false
alarm, other cause when no such danger exists, or an alarm activated by a cause that cannot be determined.
Wildland-Urban Interface Fire Area. A geographical area identified by the City of Petaluma as a “Fire Hazard
Severity Zone” in accordance with the Public Resources Code, Sections 4201 through 4204, and Government
Code, Sections 51175 through 51189, or other areas designated by the enforcing agency to be at a significant risk
from wildfires, as designated on the map titled Wildland-Urban Interface Fire Area, dated January 28, 2009. The
official map is also located electronically on the following website:
https://cityofpetaluma.org/documents/wildland-urban-interface-map/. A map of such areas is maintained in the
office of the Petaluma Fire Prevention bureau.
Section 505.1 is amended to read as follows:
505.1 Address Identification. New and existing buildings shall be provided with approved illuminated or other
approved means of address identification. The address identification shall be legible and placed in a position that
is visible from the street or road fronting the property. Address identification characters shall contrast with their
background. Address numbers shall be Arabic numerals or alphabetic letters. Numbers shall not be spelled out.
Character size and stroke shall be in accordance with Section 505.1.1 through 505.1.2. Where required by the
fire code official, address identification shall be provided in additional approved locations to facilitate emergency
response in accordance with this code and Section 505.1.3. Where access is by means of a private road and the
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 5
building cannot be viewed from the public way or when determined by the fire code official, a monument, pole,
or other approved sign or means shall be used to identify the structure. Address identification shall be maintained.
Section 505.1.1 is added to read as follows:
505.1.1 One- and Two-Family Dwellings. Numbers for one- and two-family dwellings shall be not less than
four inches (4") (101.6 mm) high with a minimum stroke width of 0.5 inches (12.7 mm).
Section 505.1.2 is added to read as follows:
505.1.2 Numbers for Other Than One- and Two-Family Dwellings. Each address identification character
shall not be less than twelve inches (12") high with a minimum stroke width of one inch (1"). Suite and unit
directional numbers shall be not less than six inches (6") in height with a minimum stroke width of three-quarter
inch (0.75"). Individual unit numbers shall not be less than four inches (4") in height with a minimum stroke
width of one-half inch (½").
Section 505.1.3 is added to read as follows:
505.1.3 Complex Directory. Where two (2) or more buildings cannot be viewed from the public way or when
determined by the Fire Code Official, an approved illuminated complex directory, monument pole, or other
approved sign or means shall be used to identify the structures at the main entrances to the property.
Chapter 7—Fire Resistance-Rated Construction
Section 709 is added to read as follows:
709 Repair of Breaches of Non-Rated Walls/Ceilings in Fire Zone 1. Breaches, openings, holes or other
broken wall and ceiling areas in buildings in "Fire Zone 1" (generally defined as the Downtown Business District)
as defined in Section 17.22 of the Petaluma Municipal Code shall be repaired, restored or replaced when
damaged, altered, breached, penetrated, removed or improperly installed. Openings/breaches can be repaired
with like material such as lath and plaster, sheetrock, plywood or other reasonable b arrier. The intent of this
Section is to close openings/breaches to limit the spread of fire and products of combustion in the downtown
business district buildings.
Chapter 9—Fire Protection and Life Safety Systems
901.6.3.2 is added to read as follows:
901.6.3.2 Records Reporting. Fire detection, alarm, and extinguishing systems shall be maintained in an
operative condition at all times and shall be replaced or repaired where defective. Non -required fire protection
systems and equipment shall be inspected, tested, and maintained or removed. All inspection, testing and
maintenance reports shall be forwarded to the Fire Department in a manner approved by the Fire Authority and
referenced by the published standards and guidelines.
901.7.6.1 is added to read as follows:
901.7.6.1 Problematic and Unreliable Fire Alarms. The Fire Code Official may determine a fire alarm to be
unreliable upon receipt of three (3) nuisance alarms within a twelve-month period. Upon making such a finding,
the Fire Code Official may order the following:
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 6
1. For any nuisance alarm where the system is not restored, the system owner must provide Fire Watch Personnel
in accordance with Fire Prevention Bureau Standards and Section 403.11.1 or take such other measures as the
Fire Code Official deems appropriate. Such measures shall remain in place until a fire department approved fire
alarm maintenance firm certifies in writing to the Fire Code Official that the alarm system has been restored to a
reliable condition, and a Fire Code Official releases the property from Fire Watch. The Fire Code Official may
require such tests as they deem necessary to demonstrate the adequacy of the system.
2. Require the owner to pay mitigation fees pursuant to the City of Petaluma fee schedule.
902.1 Definitions.
Section 902.1 is amended to add the following:
Substantial Remodel
Section 903.2 is amended to read as follows:
903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided
in the locations described in Sections 903.2.1 through 903.2.12 and Sections 903.2.14 through 903.2.21.
Approved automatic sprinkler systems in existing buildings and structures shall be provided in locations described
in Section 903.6.
Exceptions:
1. Agricultural buildings as approved by the fire code official.
2. Detached accessory structures to Group R-3 not classified as a dwelling unit and not exceeding 1,000
square feet in gross floor area located at least 50 feet from applicable building.
3. Detached noncombustible motor vehicle fuel dispensing canopies.
4. Detached Group U Occupancies not greater than 1,000 square feet.
5. Special occupancy aircraft hangar shade structures as approved by the fire code official, unless required
in NFPA 409.
Section 903.2.1 is amended to read as follows:
903.2.1 Group A. An automatic sprinkler system shall be provided throughout buildings containing a Group A
occupancy.
903.2.1.1 through 903.2.1.5.
Sections 903.2.1.1 through 903.2.1.5 are deleted.
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 7
Section 903.2.1.6 is amended to read as follows, with deletion of the exception:
903.2.1.6 Assembly occupancies on roofs. Where an occupied roof has an assembly occupancy an automatic
sprinkler system shall be provided throughout the building in accordance with Section 903.3.1.1 or 903.3.1.2.
903.2.1.7 Multiple fire areas.
Section 903.2.1.7 is deleted.
Section 903.2.2 is amended to read as follows:
903.2.2 Group B. An automatic sprinkler system shall be provided throughout buildings containing a Group B
occupancy where the gross floor area exceeds 500 square feet or as required by section 903.2.2.2.
903.2.2.1 Ambulatory care facilities. An automatic sprinkler system shall be provided throughout buildings
containing an ambulatory care facility.
Section 903.2.3 is amended to read as follows:
903.2.3 Group E. An automatic sprinkler system shall be provided throughout buildings containing Group E
occupancies. For public school State-funded construction projects or for public school campuses, kindergarten
through 12th grade, see Section 903.2.19 through 903.2.20.
Section 903.2.4 is amended to read as follows:
903.2.4 Group F. An automatic sprinkler system shall be provided throughout buildings containing a Group F
occupancy.
903.2.4.1 Woodworking operations.
Section 903.2.4.1 is deleted.
Section 903.2.5.1 is amended to read as follows:
903.2.5.1 Group H. An automatic sprinkler system shall be installed throughout buildings containing Group H
occupancies.
903.2.6.1 Group I-2
Section 903.2.6.1 is deleted.
903.2.6.2 Group I-3
Section 903.2.6.2 is amended to read as follows:
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 8
903.2.6.2 Group I-3. Every building where inmates or persons are in custody or restrained shall be protected by
an automatic sprinkler system conforming to NFPA 13. The main sprinkler control valve or valves and all other
control valves in the system shall be locked in the open position and electronically supervised so that at least an
audible and visible alarm will sound at a constantly attended location when valves are closed. The sprinkler branch
piping serving cells may be embedded in the concrete construction.
Section 903.2.7 is amended to read as follows:
903.2.7 Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M
occupancy where the gross floor area exceeds 500 square feet.
Section 903.2.8.1 is amended to read as follows:
903.2.8.1 Group R-3. An automatic sprinkler system installed in accordance with Section 903.3.1.3 shall be
permitted in Group R-3 occupancies and shall be provided throughout all one- and two-family dwellings
regardless of square footage in accordance with the California Resid ential Code. An automatic sprinkler system
shall be installed in all mobile homes, manufactured homes and multi -family manufactured homes with two or
more dwelling units in accordance with Title 25 of the California Code of Regulations.
Section 903.2.9 is amended to read as follows:
903.2.9 Group S. An automatic sprinkler system shall be provided throughout buildings containing a Group S
occupancy.
903.2.9.1 through 903.2.9.4.
Sections 903.2.9.1 through 903.2.9.4 are deleted.
903.2.10 Group S-2 Parking Garages
Section 903.2.10 through Section 903.2.10.2 is deleted.
Section 903.2.11 is amended to read as follows:
903.2.11 Specific buildings areas and hazards. In all occupancies other than detached Group U occupancies
not greater than 1,000 square feet, an automatic sprinkler system shall be installed for building design or hazard
in the locations set forth in Sections 903.2.11.1 through 903.2.11.6.
903.2.11.3 exception deleted.
Section 903.2.11.3 exception is deleted.
Section 903.2.11.7 is added to read as follows:
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 9
903.2.11.7 High-piled storage. An automatic sprinkler system shall be provided throughout buildings containing
high-pile combustible storage.
Section 903.2.11.8 is added to read as follows:
903.2.11.8 Undetermined use design. Automatic sprinkler systems installed in buildings or structures of
undetermined use shall be designed and installed to have a minimum density of .33 gallons per minute per square
foot over a minimum design area of 2,000 square feet.
Section 903.2.18 is amended to read with the exception being deleted:
903.2.18 Group U private garages and carports accessory to Group R-3 occupancies. Carports with habitable
space above and attached garages, accessory to Group R-3 occupancies, shall be protected by residential fire
sprinklers in accordance with this section. Residential fire sprinklers shall be connected to, and installed in
accordance with, an automatic residential fire sprinkler system that complies with R313 of The California
Residential Code or with NFPA 13D. Fire sprinklers shall be residential sprinklers or quick-response sprinklers,
designed to provide a minimum density of 0.05 gpm/ft2 over the most hydraulically demanding area of the
structure, but not to exceed two sprinklers for hydraulic calculations purposes. Garage doors shall not be
considered obstructions with respect to sprinkler placement.
Section 903.3 is amended as follows:
903.3 Installation Requirements. Sprinkler systems shall be designed and installed in accordance with NFPA13,
NFPA13R (if approved by the Fire Code Official) and NFPA13D. Pursuant to Section 102.7.1 and Section
105.1.4, the Fire Code Official may require additional sprinkler coverage to m itigate certain conditions such as
access or water supply issues.
Section 903.3.1 is amended to read:
903.3.1 Standards. Fire sprinkler systems installed in buildings of undetermined use shall be designed and
installed to have a design density of .33 gallons per minute per square foot over a minimum design area of three
thousand square feet (3,000' sq.). Where a subsequent occupancy change requires a system with greater capacity,
it shall be the building owners’ responsibility to upgrade the system to the required density and meet any
additional requirements of the Fire Code at the time of such change.
Section 903.3.7 is amended to read as follows:
903.3.7 Fire Department Connections. The location of fire department connections (FDCs) shall be within fifty
feet (50') of a fire hydrant or as approved by the Fire Code Official. Approved locking caps shall be provided on
any existing FDCs found to be vandalized and on new FDCs when determined by the Fire Code Official to be
necessary because of site specific conditions or hazards.
Section 903.3.9 is amended to read as follows:
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 10
903.3.9 High-rise building floor control valves. Floor control valve and waterflow detection assemblies shall
be installed at each floor where any of the following occur:
1. Buildings where the floor level of the highest story is located more than 30 feet above the lowest level of
fire department access.
2. Buildings that are three or more stories in height.
3. Buildings that are two or more stories below the highest level of fire department access.
Exception: Group R-3 and R-3.1 occupancies floor control valves and waterflow detection assemblies shall not
be required.
903.4 is amended to read as follows:
903.4 Sprinkler system supervision and alarms. Except for Group R, Division 3 Occupancies, all valves
controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels, temperatures, critical air
pressure and water flow switches shall be electronically supervised. Valves when used for standpipes are excluded
from this provision unless required by the Fire Code Official.
Section 903.4.2 is amended to read as follows:
903.4.2 Monitoring. One (1) exterior approved audible device shall be connected to every automatic fire sprinkler
system in an approved location. The Fire Code Official may require one (1) exterior audible and visual device
connected to an automatic fire sprinkler system in an approved location based on site specific conditions. Such
sprinkler water flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of
the smallest orifice size installed in the system. Where a building fire alarm system is installed, actuation of the
automatic fire sprinkler system shall actuate the building fire alarm system.
Section 903.6 is amended to read as follows:
903.6 Where required in existing buildings and structures. An automatic sprinkler system shall be provided
throughout existing buildings and structures where required in Chapter 11 and as required in this section.
Exception: Alterations made solely for the purpose of providing barrier removal pursuant to the requirements of
the Americans with Disabilities Act (ADA) as contained in exception #4 of Section CBC 11B-202.4.
Section 903.6.1 – Section 903.6.5 is added to read as follows:
Note: The December 31, 2029 compliance date was adjusted to allow additional time for regulatory adherence
due to the impacts of COVID-19.
Section 903.6.1 is added to read as follows:
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 11
903.6.1 Buildings that undergo a substantial remodel.
Building that qualify as a substantial remodel as defined by section 202 of this code, must install automatic
sprinklers according to the policy on file and available through the City of Petaluma Fire Prevention Bureau.
903.6.2 Changes of Occupancy. When any change of occupancy occurs where the proposed new occupancy
classification is more hazardous based on fire and life safety risks as determined by the Fire Code Official
including, but not limited to, the conversion of residential buildings to condominiums, the building shall meet the
fire sprinkler requirements for a newly constructed building.
903.6.3 Residential Conversions. Fire sprinkler systems shall be installed in all single-family dwellings that are
converted to duplexes and/or multi-family dwellings, bed and breakfasts, inns, lodging houses or similar uses.
Fire sprinkler systems shall be installed in all conversions of a detached garage into living space or sleeping space.
903.6.4 Elevation of Existing Buildings. An automatic fire extinguishing system shall be installed throughout
all existing buildings when the building is elevated to three (3) or more stories or more than thirty -five feet (35')
in height, from grade to the exposed roof.
Exceptions: An automatic fire-extinguishing system need not be provided when the area above thirty-five feet
(35') is provided for aesthetic purposes only and is a non-habitable space.
903.6.5 Installation of Automatic Fire Sprinklers in Pre-Existing Buildings (Historic Downtown Business
District).
1. Geographic Boundary—Historic Downtown Business District: For the purposes of this section, the Historic
Downtown Business District shall include all buildings located inside the geographic area generally formed by
Kentucky Street to the west, Washington Street to the north, the Petaluma River to the east and B Street to the
south. Also included in this section is 201 Washington Street (Phoenix Theater) and 132 Keller Street, as more
particularly described in Figure 1003.2.12.
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 12
2. Installation Requirements: An automatic sprinkler system conforming to the Standard for the Installation of
Sprinkler Systems (NFPA 13) shall be installed in all existing buildings in the Historic Downtown Business
District in accordance with the following criteria:
2.1. Kentucky Street, Western Avenue, Petaluma Boulevard North:
2.1.1. In any building wherein a change of occupancy occurs.
2.1.2. In any building or occupancy where the square footage of the building or occupancy is increased or
alterations to the structure are made pursuant to Section 903.6 of this Ordinance.
2.1.3. All buildings with basements or space below street grade used for storage, business or public use shall have
automatic fire sprinklers installed within the basements or the below street grade areas.
2.2. Property Owner’s Responsibility for System Installation:
2.2.1. The Property Owner shall be responsible for installation of the lateral service from the curb line into the
building. This also includes isolation, check or other valves or devices, as applicable.
2.2.2. The Property Owner shall be responsible for the installation of the automatic fire sprinkler system according
to the Standard for the Installation of Sprinkler Systems (NFPA 13).
2.2.3 All buildings not meeting the criteria of 2.1.1 or 2.1.2 above shall have automatic fire sprinklers installed
throughout the structure, including all public, private, storage and/or concealed spaces, as defined by the Standard
for the Installation of Sprinkler Systems (NFPA 13) by no later than December 31, 2029.
2.3. Plans and Specifications: Plans and Calculations (NFPA 13, Chapter 8) for the service lateral and fire
sprinkler system shall be submitted to and approved by the Fire Prevention Bureau prior to installation of
equipment and materials. All Plans and Calculations for service lateral and sprinkler systems shall be submitted
no later than June 30, 2029, with installation and approval of work to occur prior to December 31, 2029.
Section 905.3.1 is amended to read as follows:
905.3.1 Height. Class I standpipes shall be installed in buildings three stories or over in height and/or if, in the
opinion of the Fire Chief or Fire Marshal, a hazard or condition exists in which the installation of standpipes
would improve firefighting operations. Standpipes will be provided with approved outlets provided on each floor
level, including the roof when roof access is provided.
Section 905.9: exception 2 is deleted.
Section 907.8.5 is added to read as follows:
907.8.5 Fire Alarm Service/Certification Stickers/Tags. Upon completion of each annual fire alarm service,
the licensed fire alarm contractor providing the service shall affix a certification sticker or tag to the front of the
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 13
main fire alarm panel which indicates the name of the fire alarm company, the date of the service, and the State
license number.
Chapter 15 Roof Assemblies And Rooftop Structures
Section 1505.1 is amended to read as follows:
1505.1 General. Roof assemblies shall be minimum Class A roof assemblies . Class A roof assemblies and
roof coverings required to be listed by this section shall be tested in accordance with ASTM E108 or UL 790. In
addition, fire-retardant-treated wood roof coverings shall be tested in accordance with in accordance with ASTM
D2898.
Exception: Skylights and sloped glazing that comply with Chapter 24 or Section 2610.
Table 1505.1 is deleted.
Section 1505.1.1 is amended to read as follows, with the exception deleted:
1505.1.1 Roof coverings within very-high fire hazard severity zones, state responsibility areas and all other
areas. The entire roof covering of every existing structure where more than 50 percent of the total roof area is
replaced within any one-year period, the entire roof covering of every new structure and any roof covering
applied in the alteration, repair or replacement of the roof of every existing structure, shall be fire-retardant
covering that is at least Class A.
Sections 1505.1.2 and 1505.1.3 are deleted.
Sections 1505.3, 1505.4, and 1505.5 are deleted.
Section 1505.6 is amended to add the following exception:
Exception: Fire-retardant-treated wood shingles and shakes are prohibited in wildland-urban interface areas.
Table 1505.7 is amended to add the following exception:
Exception: Fire-retardant-treated wood shingles and shakes are prohibited in wildland-urban interface areas.
Chapter 18 Soils and Foundations
Section 1803.1.1.1 is amended as follows:
A preliminary soil report, prepared by a civil engineer who is registered by the state shall be provided for each
subdivision. The report shall be based upon adequate test borings or excavations, of every subdivision, where a
tentative and final map is required pursuant to Section 66426 of the Government Code.
The preliminary soil report may be waived if the building department of the city, county, or city and county, or
other enforcement agency charged with the administration and enforcement of the provisions of Section
1803.1.1, shall determine that, due to the knowledge such department has as to the soil qualities of the soil of the
subdivision or lot, no preliminary analysis is necessary.
Section 1803.1.1.2 is amended as follows:
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 14
1803.1.1.2. Soil investigation by lot, necessity, preparation and recommendations. If the preliminary soil report
indicates the presence of critically expansive soils or other soil problems which, if not corrected, would lead to
structural defects, a soil investigation of each lot in the subdivision is required.
The soil investigation shall be prepared by a civil engineer who is registered in this state. It shall recommend
corrective action which is likely to prevent structural damage to each dwelling proposed to be constructed on the
site where hazardous soil conditions are present. For each specific construction site or lot, the geotechnical
engineer shall provide such investigation and recommendations, or letter of exemption from this section.
1803.1.1.3. Approval, building permit conditions, appeal.
The building department or other enforcement agency charged with the administration and enforcement of the
provisions of Section 1803.1.1, shall approve the soil investigation if it determines that the recommended action
is likely to prevent structural damage to each dwelling to be constructed. A condition to the building permit, shall
require that the approved recommended action be incorporated in the construction of each dwelling. Appeal from
such determination shall be to the local appeals board.
Part 2.5 of the 2025California Building Standards Code, California Residential Code, as adopted in section
17.04.010, is hereby amended to include the following additions, amendments, and deletions:
California Residential Code
Chapter 1 Administration
Section R105.2 1. is hereby amended to read as follows:
R105.2. Building 1.: One-story detached accessory structures used as tool and storage sheds, playhouses and
similar uses, provided the floor area is not greater than one hundred twenty square feet (120 sq.) (11 m2), there
are no wall finishes such as, but not limited to, gypsum wallboard, plaster, stucco, or paneling placed on any
interior surface of any wall and/or partition, and no electrical, mechanical or plumbing systems are contained
within the structure. These structures are still regulated by Section 710A, despite exemption from permit.
Section 109.3 is amended to read as follows:
The applicant for a permit shall provide an estimated value of the work for which the permit is being issed at
time of application. Such estimated valuation shall include the total value of work, including materials and labor,
for which the permit is being issued, such as electrical, gas, mechanical, plumbing equipment and permanent
systems. Where, in the opinion of the building official, the valuation is underestimated, the permit shall be denied,
unless the applicant can show detailed estimates acceptable to the building official. The building official shall
have the authority to adjust the final valuation for permit fees.
Section R114.1 and R114.2 are hereby amended to read as follows. A new section R114.5 is created:
R114.1 Authority. Where the building official finds any work regulated by this code being performed in a
manner contrary to the provisions of this code or in a dangerous or unsafe manner, without a permit, beyond the
scope of the issued permit, in violation of the Petaluma Municipal Code or Zoning Ordinance, the building
official is authorized to issue a stop work order.
R114.2 Issuance. The stop work order shall be in writing, be posted in a visible location near the location where
the work is being conducted, and shall be given to the owner of the property, the owner’s authorized agent or the
person performing the work. Upon issuance of a stop work order, the cited work shall immediately cease. The
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 15
stop work order shall state the reason for the order and the conditions under which the cited work is authorized
to resume.
R114.5—Fee. An additional investigation fee of at least the permit fee and up to five times the permit fee shall
be added to each permit subject to a stop work order or notice of violation, according to the building official’s
determination. Licensed contractors and repeat offenders are to be assessed investigation fee at five times the
permit fee.
Chapter 2 – Definitions
Section R202, General Definitions is amended to amend and add the following:
JUNIOR ACCESSORY DWELLING UNIT. [HCD] A unit that is no more than 500 square feet in size and
contained entirely within an existing single-family structure. A junior accessory dwelling unit may include
separate sanitation facilities, or may share sanitation facilities with the existing structure. (See Government Code
Section 65852.22.)
KITCHEN. That portion in a residential dwelling unit that is a room or area used for cooking, food storage and
preparation and washing dishes, including associated counter tops and cabinets, refrigerator, stove, ovens and
floor area.
Substantial Remodel. Any repair, reconstruction, rehabilitation, alteration, addition or other improvement of a
building or structure that is any of the following:
(1) An existing building or structure not classified as Group R-3 occupancy that undergoes any addition of
floor area that is equal to or exceeds 10 percent of the existing gross floor area of the building or structure.
(2) An existing building or structure classified as a Group R-3 occupancy that undergoes any addition of
floor area that is equal to or exceeds 50 percent of the existing gross floor area of the building or structure.
(3) An existing building or structure that undergoes any combination of repair, reconstruction, rehabilitation,
alteration, addition or other improvement to floor area of the building or structure that is equal to or
exceeds 50 percent of the existing gross floor area of the building or structure.
(4) If in the determination of the Building Official a building or structure has sustained substantial damage,
as defined by Section 202 of the California Building Code as amended hereby, any combination of repair,
reconstruction, rehabilitation, alteration, addition or other improvement are considered substantial
improvement regardless of the actual work performed.
The Code Official shall aggregate any combination of repair, reconstruction, rehabilitation, alteration, addition,
or other improvements to a building or structure within a three (3) year period, and if the combined affected
gross floor area of the building or structure is equal to or exceeds 50% of gross floor area of the building or
structure, the aggregated work shall constitute substantial improvement and the building shall be subject to the
fire sprinkler requirement.
Nuisance Alarm. An unwarranted alarm caused by mechanical failure, malfunction, improper installation or
lack of proper maintenance, system servicing testing, construction activities, ordinary household activities, false
alarm, other cause when no such danger exists, or an alarm activated by a cause that cannot be determined.
Wildland-Urban Interface Fire Area. A geographical area identified by the City of Petaluma as a “Fire Hazard
Severity Zone” in accordance with the Public Resources Code, Sections 4201 through 4204, and Government
Code, Sections 51175 through 51189, or other areas designated by the enforcing agency to be at a significant risk
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 16
from wildfires, as designated on the map titled Wildland-Urban Interface Fire Area, dated January 28, 2009. The
official map is also located electronically on the following website:
https://cityofpetaluma.org/documents/wildland-urban-interface-map/. A map of such areas is maintained in the
office of the Petaluma Fire Prevention bureau.
Chapter 3 – Building Planning
Section R301.2 is amended by inserting the following Table R301.2(1).
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 17
TABLE R301.2(1). CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA
GROUN
D SNOW
LOAD o
WIND DESIGN SEISMIC
DESIGN
CATEGORY
f
SUBJECT TO DAMAGE FROM WINTER
DESIGN
TEMP e
ICE BARRIER
UNDERLAYME
NT REQUIRED h
FLOOD
HAZARDS g
AIR
FREEZIN
G INDEX i
MEAN
ANNUA
L TEMP
j
d
(mph)
Topographic
k
Special
wind
l
Windborne
m
Weathering Frost line
depth b
Termite c
0 110 NO NO N/A D2 or E
Reference
Table
R301.2.2.1.1
See mapping
tools:
www.seismic
maps.org
Negligible 12 inches Yes 32 degrees
F
NO Initial NFIP
Map Date:
March 8, 1974.
Initial FIRM
date: February
15, 1980.
Current Flood
Insurance
Study dated:
February 19,
2014.
Panels 982,
1001, 1002,
1003, and
1004 are dated
October 2,
2015.
Panels 891,
893, 894, and
913 are dated
February 19,
2014.
1 degree F 58
degrees F
MANUAL J DESIGN CRITERIA n
Elevation Latitude Winter heating Summer cooling Altitude correction
factor
Indoor design
temperature
Design temperature
cooling
Heating temperature
difference
87 FT 38 degrees North. 29 degrees F. 90 degrees F. N/A 68 degrees F. 75 degrees F. 39 degrees F.
Cooling temperature difference Wind velocity
heating
Wind velocity
cooling
Coincident wet
bulb
Daily range Winter humidity Summer humidity —
15 degrees F. N/A N/A 67 degrees F. High. 31 degrees F. N/A N/A —
For SI: 1 pound per square foot = 0.0479 kPa, 1 mile per hour = 0.447 m/s.
a. Where weathering requires a higher strength concrete or grade of masonry than necessary to satisfy the structural requirem ents of this code, the frost line depth strength required for weathering shall govern.
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 18
The weathering column shall be filled in with the weathering index, “negligible,” “moderate” or “severe” for concrete as dete rmined from Figure R301.2(4). The grade of masonry units shall be determined from
ASTM C34, C55, C62, C73, C90, C129, C145, C216 or C652.
b. Where the frost line depth requires deeper footings than indicated in Figure R403.1(1), the frost line depth strength required for weathering shall govern. The jurisdiction shall fill in the frost line depth column
with the minimum depth of footing below finish grade.
c. The jurisdiction shall fill in this part of the table to indicate the need for protection depending on whether there has been a history of local subterranean termite damage.
d. The jurisdiction shall fill in this part of the table with the wind speed from the basic wind speed map [Figure R301.2(5)A ]. Wind exposure category shall be determined on a site-specific basis in accordance
with Section R301.2.1.4.
e. The outdoor design dry-bulb temperature shall be selected from the columns of 97-1/2 -percent values for winter from Appendix D of the International Plumbing Code. Deviations from the Appendix D
temperatures shall be permitted to reflect local climates or local weather experience as determined by the building official. [Also see Figure R301.2(1).]
f. The jurisdiction shall fill in this part of the table with the seismic design category determined from Section R301.2.2.1.
g. The jurisdiction shall fill in this part of the table with (a) the date of the jurisdiction’s entry into the National Floo d Insurance Program (date of adoption of the first code or ordinance for management of flood
hazard areas), (b) the date(s) of the Flood Insurance Study and (c) the panel numbers and dates of the currently effective FIRMs and FBFMs or other flood hazard ma p adopted by the authority having jurisdiction,
as amended.
h. In accordance with Sections R905.1.2, R905.4.3.1, R905.5.3.1, R905.6.3.1, R905.7.3.1 and R905.8.3.1, where there has been a history of local damage from the effects of ice damming, the jurisdiction shall
fill in this part of the table with “YES.” Otherwise, the jurisdiction shall fill in this part of the table with “NO.”
i. The jurisdiction shall fill in this part of the table with the 100-year return period air freezing index (BF-days) from Figure R403.3(2) or from the 100-year (99 percent) value on the National Climatic Data Center
data table “Air Freezing Index-USA Method (Base 32°F).”
j. The jurisdiction shall fill in this part of the table with the mean annual temperature from the National Climatic Data Center data table “Air Freezing Index-USA Method (Base 32°F).”
k. In accordance with Section R301.2.1.5, where there is local historical data documenting structural damage to buildings due to topographic wind speed-up effects, the jurisdiction shall fill in this part of the table
with “YES.” Otherwise, the jurisdiction shall indicate “NO” in this part of the table.
l. In accordance with Figure R301.2(5)A, where there is local historical data documenting unusual wind conditions, the jurisd iction shall fill in this part of the table with “YES” and identify any specific
requirements. Otherwise, the jurisdiction shall indicate “NO” in this part of the table.
m. In accordance with Section R301.2.1.2 the jurisdiction shall indicate the wind -borne debris wind zone(s). Otherwise, the jurisdiction shall indicate “NO” in this part of the table.
n. The jurisdiction shall fill in these sections of the table to establish the design criteria using Table 1a or 1b from ACCA Manual J or established criteria determined by the jurisdiction.
o. The jurisdiction shall fill in this section of the table using the Ground Snow Loads in Figure R301.2(6).
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 19
Section R313.1 is amended, with the exceptions replaced as follows:
R309.1 Townhouse automatic fire sprinkler systems. An automatic residential fire sprinkler system shall be
installed in townhouses .
Exceptions:
1. Accessory Dwelling Unit, provided that all of the following are met:
1.1. The unit meets the definition of an Accessory Dwelling Unit as defined in Government Code Section 65852.2.
1.2. The existing primary residence does not have automatic fire sprinklers.
1.3. The accessory detached dwelling unit does not exceed 1,200 square feet in size.
1.4. The unit is on the same lot as the primary residence.
1.5. The accessory dwelling unit meets the requirements of California Fire Code, Sections 503.1.1 and 507.5.1.
2. Detached accessory structures to Group R-3 not classified as a dwelling unit and not exceeding 1,000 square
feet in gross floor area located at least 50 feet from applicable building.
3. Detached Group U Occupancies not greater than 1,000 square feet.
Section R309.1.2.1.2 is added as follows:
R309.1.2 Substantial Remodel. An automatic fire sprinkler system shall be provided throughout all Townhouses
that undergo a substantial improvement.
Section R309.2 is amended to read as follows, with the exception deleted:
R309.2 One- and two-family dwellings automatic fire sprinkler systems. An automatic residential fire
sprinkler system shall be installed in townhouses. Group R-3 occupancies permitted under this code shall be
provided throughout regardless of square footage with an automatic sprinkler system inclusive of all mobile
homes, manufactured homes.
Exceptions:
1. Accessory Dwelling Unit, provided that all of the following are met:
1.1. The unit meets the definition of an Accessory Dwelling Unit as defined in Government Code Section 65852.2.
1.2. The existing primary residence does not have automatic fire sprinklers.
1.3. The accessory detached dwelling unit does not exceed 1,200 square feet in size.
1.4. The unit is on the same lot as the primary residence.
1.5. The accessory dwelling unit meets the requirements of California Fire Code, Sections 503.1.1 and 507.5.1.
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 20
2. Detached accessory structures to Group R-3 not classified as a dwelling unit and not exceeding 1,000 square
feet in gross floor area located at least 50 feet from applicable building.
3. Detached Group U Occupancies not greater than 1,000 square feet.
Section R309.2.2 is added as follows:
R313.2.2 Substantial Remodel. An automatic fire sprinkler system shall be provided throughout all one- and
two-family dwellings that undergo a substantial improvement.
Chapter 4 Foundations
Section R401.1 is amended as follows:
R401.4.1.1 General and where required for applications listed in Section 1.8.2.1.1 regulated by the Department
of Housing and Community Development. Foundations and soils investigations shall be conducted in
conformance with Health and Safety Code Sections 17953 through 17957 as summarized below.
A preliminary soil report, prepared by a civil engineer who is registered by the state shall be provided for each
subdivision. The report shall be based upon adequate test borings or excavations, of every subdivision, where a
tentative and final map is required pursuant to Section 66426 of the Government Code.
The preliminary soil report may be waived if the building department of the city, county, or city and county, or
other enforcement agency charged with the administration and enforcement of the provisions of Section
R401.4.1.1, shall determine that, due to the knowledge such department has as to the soil qualities of the soil of
the subdivision or lot, no preliminary analysis is necessary.
Section R401.4.1.1.2 is amended as follow:
R401.4.1.1.2 Soil investigation by lot, necessity, preparation and recommendations.
If the preliminary soil report indicates the presence of critically expansive soils or other soil problems, which if
not corrected, would lead to structural defects, a soil investigation of each lot in the subdivision is required.
The soil investigation shall be prepared by a civil engineer who is registered in this state. It shall recommend
corrective action which is likely to prevent structural damage to each dwelling proposed to be constructed on the
site where hazardous soil conditions are present. For each specific construction site or lot, the geotechnical
engineer shall provide such investigation and recommendations, or letter of exemption from this section based on
site and lot specific soil conditions supporting such letter of exemption.
Section R401.4.1.1.3 is amended as follows:
R401.4.1.1.3. Approval, building permit conditions, appeal.
The building department or other enforcement agency charged with the administration and enforcement of Section
401.4.1.1, shall approve the soil investigation if it determines that the recommended action is likely to prevent
structural damage to each dwelling to be constructed. A condition to the building permit, shall require that the
approved recommended action be incorporated in the construction of each dwelling. Appeal from such
determination shall be to the local appeals board.
Chapter 9 Roof Assemblies
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 21
Section R902.1 is amended to read as follows:
R902.1 Roof covering materials. Roofs shall be covered with materials as set forth in Section R904 and R905.
A minimum Class A roofing shall be installed in all areas. Class A roofing required by this section to be listed
shall be tested in accordance with UL 790 or ASTM E108.
Section R902.1.1 is amended to read as follows:
R902.1.1 Roof coverings within very-high fire hazard severity zones, state responsibility areas and all other
areas. The entire roof covering of every existing structure where more than 50 percent of the total roof area is
replaced within any one-year period, the entire roof covering of every new structure and any roof covering applied
in the alteration, repair or replacement of the roof of every existing structure, shall be fire-retardant covering that
is at least Class A.
Section R902.2 is amended to add the following exception:
Exception: Fire-retardant-treated wood shingles and shakes are prohibited in wildland-urban interface areas.
Table R902.4 is amended to add the following exception:
R902.4 Rooftop-mounted photovoltaic panel systems. Rooftop-mounted photovoltaic panel systems installed
on or above the roof covering shall be tested, listed and identified with a fire classification in accordance with UL
1703 and UL 2703. Class A photovoltaic panel systems and modules shall be installed in all areas, in jurisdictions
designated by law as requiring their use.
Part 8 of the 2025 California Building Standards Code, California Historical Building Code, as adopted in section
17.04.010, is hereby amended to include the following additions, amendments and deletions:
Historical Building Code
Section 8-410.1 is amended to read as follows: (exception added)
Exception: Historical Buildings within the Historic Downtown Business District shall comply with Petaluma
Municipal code Section 903.6.5
Part 10 of the 2025 California Existing Building Code, as adopted in section 17.04.010, is hereby amended to
include the following additions, amendments, and deletions:
Existing Building Code
Chapter 2 is hereby amended to include the following definition:
Section 202.
Substantial Remodel. Any repair, reconstruction, rehabilitation, alteration, addition or other improvement of a
building or structure that is any of the following:
(1) An existing building or structure not classified as Group R-3 occupancy that undergoes any addition of
floor area that is equal to or exceeds 10 percent of the existing gross floor area of the building or structure.
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 22
(2) An existing building or structure classified as a Group R-3 occupancy that undergoes any addition of
floor area that is equal to or exceeds 50 percent of the existing gross floor area of the building or structure.
(3) An existing building or structure that undergoes any combination of repair, reconstruction, rehabilitation,
alteration, addition or other improvement to floor area of the building or structure that is equal to or
exceeds 50 percent of the existing gross floor area of the building or structure.
(4) If in the determination of the Building Official a building or structure has sustained substantial damage,
as defined by Section 202 of the California Building Code as amended hereby, any combination of repair,
reconstruction, rehabilitation, alteration, addition or other improvement are considered substantial
improvement regardless of the actual work performed.
The Code Official shall aggregate any combination of repair, reconstruction, rehabilitation, alteration, addition,
or other improvements to a building or structure within a three (3) year period, and if the combined affected
gross floor area of the building or structure is equal to or exceeds 50% of gross floor area of the building or
structure, the aggregated work shall constitute substantial improvement and the building shall be subject to the
fire sprinkler requirement.
Part 11 of the 2025 California Building Standards Code, California Green Building Standards Code, as adopted
in section 17.04.010, is hereby amended to include the following additions, amendments, and deletions:
Green Building Standards Code
Appendix A4, Division A4.2 Energy Efficiency is deleted.
Appendix A5, Division A5.2 Energy Efficiency is deleted.
EXHIBIT A
FINDINGS OF FACT AND NEED FOR CHANGES OR MODIFICATIONS TO THE CALIFORNIA
BUILDING, RESIDENTIAL, HISTORICAL, GREEN BUILDING STANDARDS, AND ELECTRICAL
CODES, 2025 EDITION WITH CALIFORNIA AMENDMENTS, DUE TO LOCAL CONDITIONS
CLIMACTIC
Precipitation: Precipitation ranges from twenty inches (20”) to approximately twenty-five inches (25”) per year.
Approximately ninety percent (90%) falls during the months of November through April, and ten percent (10%)
from May through October. Severe flooding occurred during the months of January and March, 1995 and in 1998
and 2006.
Relative Humidity: Humidity generally ranges from fifty percent (50%) during daytime and eighty -six percent
(86%) at night. It drops to twenty-percent (20%) during the summer months and occasionally drops lower during
the months of September through November.
Temperatures: Temperatures have been recorded as high as 104 degrees Fahrenheit. Average summer highs are
in the 78-85 degree range.
Winds: Prevailing winds are from the northwest. However, winds are experienced from virtually every direction
at one time or another. Velocities are generally in the 5-15 mph range, gusting to 30 mph, particularly during the
summer months. High wind gusts with speeds, up to 50 mph, have been known to occur. The City is not in a
special wind region as defined in the building code.
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 23
Soils: Much of Petaluma has "Adobe" type soil. This soil generally has high clay content, high plasticity, and is
high to very high expansion potential to exert significant pressures on concrete foundations, slabs and flatwork.
With Petaluma's dry summers and wet winters, the moisture content of the soil varies greatly during the course
of the year. This moisture content change causes expansion/contraction of the clay soil. This
expansion/contraction can place significant loads on concrete slabs and foundation systems making some
"standard" foundation methods/materials inappropriate for the local conditions encountered. Geotechnical
investigations are essential for finding cost effective solutions for mitigating effects of these soils in designing
new foundations.
CBC Appendix Q – Emergency Housing is adopted to supplement efforts for assisting local populations of
unhoused individuals and is applicable to emergency housing and emergency housing facilities, as defined.
CRC Appendix CJ – Emergency Housing is adopted to supplement efforts to assist local populations of unhoused
individuals and is applicable to emergency housing and emergency housing facilities, as defined in AZ102.
CRC Appendix BG – Sound Transmission is adopted to provide multi-family housing to have environmental
standards for noise reduction.
CRC Appendix BI - Light Straw-Clay Construction is adopted to support alternatives to traditional wood light-
frame construction. The advantages of light straw-clay construction include thermal performance, sustainable
materials choices, and low environmental impact.
CalGreen Tier 1 requirements are adopted in Appendix A4 and A5 to achieve a greater level of sustainability for
the local environment. Appendices sections A4.2 and A5.2 are deleted to maintain mandatory energy compliance.
Mandatory energy efficiency requirements in new buildings in this climate zone are sufficient to serve our
community’s climatic and environmental conditions.
TOPOGRAPHIC
The topographic environment of a community is primarily a combination of two (2) factors: the area's physical
geographic characteristics and the historic pattern of urban-suburban development. These two (2) factors, alone
and combined, create a mixture of environments which ultimately determine the needs of the City of Petaluma's
Building regulations.
The basic geographical boundaries of the city include hills to the south and west, and valley floor in the central
area and to the north and east. The Petaluma River bisects the city through the central area. The City of Petaluma
covers 13 square miles, including an urban population estimated at 58,000. The city’s service area is a
conglomeration of bay, plains, hills, valleys, and ridges.
CBC Appendix N - Replicable Buildings is adopted to allow Petaluma to recover from a natural disaster faster
and allow for consistent application of the codes for replicable building projects. It will result in faster turnaround
for the end user, and a quicker turnaround through the plan review process.
CRC Appendix BH – Automatic Vehicular Gates is adopted for safety of residential gates common in our area
and provides requirements for automatic vehicular gates, including a definition of and references to standards that
regulate such gates.
CRC Appendix BB – Tiny Houses is adopted to afford increased safety in small residential structures that are
becoming common in our community. These provisions apply to houses that are 400 square feet in area or less.
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 24
Attention is specifically paid to features such as compact stairs, including stair handrails and headroom, ladders,
reduced ceiling heights in lofts and guard and emergency escape and rescue opening requirements at lofts.
GEOLOGICAL
The relatively young geological processes that have created the San Francisco Bay Area are still active today.
Two (2) active earthquake faults (San Andreas and the Hayward-Rodgers Creek) affect the Petaluma area.
Approximately fifty percent (50%) of the city's land surface is in the high-to-moderate seismic hazard zones.
Many of the soils found throughout the City of Petaluma are highly expansive adobe type soils. The combination
the highly expansive nature of these soils along with the long dry summers followed by a compressed rainy season
create high stresses on building foundation systems, as such some simpler types of foundation systems are not
adequate for these soils conditions.
CBC Section 1803.1.1 is adopted to clarify requirements for subdivision soil investigations in accordance with
Health and Safety Code Sections 17953 through 17957. The Petaluma conditions include the presence of
expansive soils and geologically active conditions.
CBC Appendix J - Grading is adopted and requires specific grading projects to be designed and permitted safely.
This appendix supplements the Municipal Code, Chapter 17.31 Grading and Erosion Control. As there are no
"isolated, self-contained" areas within City limits, the Grading Permit exception J103.2 (1) was removed for
clarity.
PROCEDURAL CLARIFICATION
Changes to CBC Section 115 and CRC R114 regarding Stop Work Order are made to clarify the authority,
issuance, and fees applicable to violations.
DEFINITION CLARIFICATION
Due to code enforcement problems in the past, CBC Section 105.2 Exemptions from permits is amended to
include description of buildings not requiring permits and expanded to help clarify when permits are/are not
required.
Definitions for Junior ADU, Kitchen, and Efficiency Kitchens are added to the CBC and CRC to clarify the
characteristics of a JADU as distinct from the defined ADU and to clarify the required Efficiency Kitchen as
distinct from a Kitchen required for a Dwelling.
CONTINUITY
All the amendments to Chapters 7, 9, and 15 of Part 2 (Building Code) of the California Building Standards Codes
contained in this Ordinance are made so that they reflect amendments to chapters 7 and 9 of Part 9 (Fire Code) of
the California Building Standards Code made through a separate Ordinance sponsored by the Fire Marshal’s
Office.
Amendments to the California Residential Code Part 2.5 of the California Building Standards Codes in Chapters
2, 3, and 9 are likewise intended to provide continuity with the Fire Code. Amendment to the California Historical
Code Part 8 is made to ensure continuity with Fire Code adoption in the Historic Downtown Business District
area.
SUMMARY
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 25
These local climatic conditions require local code amendment for the safety of the city communities.
CONCLUSION
That each of the changes or modifications to measures referred to herein are reasonably necessary because of
local climatic, geographical, or topographical conditions in the area encompassed by the boundaries of the City
of Petaluma and the findings set forth in Exhibit A are hereby adopted and support the local necessity for the
changes or modifications.
SECTION 4. SEVERABILITY. If any part of this Ordinance is for any reason held to be unconstitutional,
unlawful or otherwise invalid by a court of competent jurisdiction, such decision will not affect the validity of the
remaining parts of this Ordinance. The City Council of the Ci ty of Petaluma hereby declares that it would have
passed and adopted this Ordinance and each of its provisions irrespective of any part being held invalid.
SECTION 5. CEQA. The City Council finds that this Ordinance is not subject to the California Environmental
Quality Act (“CEQA”) pursuant to Section 15060(c)(2) of the CEQA Guidelines because the activity has no
potential for resulting in a direct or reasonably foreseeable indirect physical change in the environment, and
pursuant to Section 15060(c)(3) of the CEQA Guidelines because the activity is not a project as defined in Section
15378) of the CEQA Guidelines.
If this ordinance were a “project” pursuant to CEQA it would be exempt pursuant to CEQA Section 15061(b)(3)
(common sense exemption) since this action involves updates and revisions to existing regulations consistent with
State law and will not result in any direct or indirect physical changes to the environment The proposed
amendments are also exempt from CEQA in accordance with Section 15307 of the CEQA Guidelines as an action
taken by the City as authorized by state law to assure the maintenance, restoration or enhancement of a natural
resource where the regulatory process involves procedures for protection of the environment, in accordance with
the findings in the attached ordinance. The proposed amendments are also exempt from CEQA in accordance
with Section 15308 of the CEQA Guidelines as an action taken by the City as authorized by state law to assure
the maintenance, restoration, enhancement, or protection of the environment where the regulatory process
involves procedures for protection of the environment in accordance with the findings in the attached ordinance.
Additionally, most of the regulatory standards imposed by this ordinance apply to interior modifications.
Proposed modifications to the interior of a home do not constitute a project subject to CEQA because such changes
are not visible or perceptible outside the home. (Martin v. City and County of San Francisco (2005) 135 Cal. App.
4th 392.)
SECTION 6. OTHER SECTIONS REMAIN IN EFFECT. Other sections and chapters of Title 17 of the Petaluma
Municipal Code not amended by this Ordinance remain in full force and effect and are hereby readopted in their
entirety with all their original findings.
SECTION 7. EFFECTIVE DATE/REFERENDUM PERIOD/URGENCY FINDINGS. This ordinance shall
become effective on the later date of January 1, 2026, or thirty (30) days after the date of its adoption by the
Petaluma City Council and filing of this ordinance with the California Building Standards Commission in
accordance with the requirements of Health & Safety Code Section 17958.7.
SECTION 8. POSTING/PUBLISHING OF NOTICE. The City Clerk is hereby directed to post and/or publish
this ordinance or a synopsis of it for the period and in the manner required by the City Charter. The City Clerk is
also hereby directed to file a Notice of Exemption concerning this ordinance with t he Office of the Sonoma
County Clerk in accordance with Section 15062 of the CEQA Guidelines. In accordance with California Health
and Safety Code Section 17958.7, the City Clerk is hereby authorized and directed to file this Ordinance and the
attached findings of fact with the California Building Standards Commission, the Department of Housing and
Docusign Envelope ID: 3D54D193-85F4-4DD6-9817-96E9889AEE72
Ordinance No. 2914 N.C.S. Page 26
Community Development, the State Fire Marshal, and the State Historical Building Safety Board prior to the
effective date of this Ordinance specified above.
SECTION 9. DECEMBER 1, 2025, PUBLIC HEARING DATE. Sets a public hearing date of December 1,
2025, during the regular City Council meeting for the adoption and second reading of this ordinance.
INTRODUCED and ordered posted/published this 17th day of November 2025.
ADOPTED this 1st day of December 2025 by the following vote:
Ayes: McDonnell, Barnacle, Cader Thompson, DeCarli, Nau, Quint, Shribbs
Noes: None
Abstain: None
Absent: None
Kevin McDonnell, Mayor
ATTEST: APPROVED AS TO FORM:
Caitlin Corley, City Clerk Eric Danly, City Attorney